Unit Type Jumpers; Heat Stage Jumper Positions; Air Temperature Sensor Connections - Lennox iComfort E30 Installation And Setup Manual

Smart thermostat
Hide thumbs Also See for iComfort E30:
Table of Contents

Advertisement

Table 3. Conventional Terminals (24VAC)
Label
Description
Function
Used as reversing valve output for heat pumps. The EIM uses
a single-pole dual throw relay to generate O and B signals.
Heat pump reversing
O
Normally the O output is open and B output at 24VAC during
valve (24VAC = cool)
heating calls. During cooling calls O is 24VAC and B open.
With relay de- energized 24VAC is present on O terminal.
Heat pump reversing
When power off/ or control reset, 24VAC power shall not be
B
valve (24 VAC = heat)
present on the O terminal.
u
t
J
nit
ypE
umpErs
Set the unit type jumper for the type of indoor unit being used (see figure 2 and
table 4). The factory default setting is IFC. If jumper is missing from header, alarm
130 is activated.
Table 4. Unit Type Jumpers Positions
Jumper
Indoor Unit
Position
HP
DO NOT USE
IFC
Conventional Furnace
AHC
Conventional Air Handler
HP
DO NOT
USE
Figure 3. Unit Type Jumper Positions
h
s
J
p
Eat
tagE
umpEr
ositions
The heat staging Jumper must be set for the number of stages of electric heat (air
handler) or the number of stage of gas heat (furnace) and stages of heat pump.
Using the heat stages jumper (see figure 3 and table 8).
The factory default setting is position 2. If jumper is missing from header, alarm 130
is activated.
0
Figure 4. Heat Stage Jumper Positions
Outdoor Unit
Conventional Heat Pump or air condition-
er
IFC
AHC
1
2
3
Table 5. Heat Stage Jumpers
Air Handler Heat
Stages
Label
(Position)
No Electric
0
0
Heat
1
1
100%
2
2
50%, 100%
(default)
33.5%,
3
3
66.5%,
100%
NOTE:
If jumper is missing, setting defaults to single stage. Changing jumper position after pow-
er-up requires recommission for the change to be recognized.
a
t
s
C
ir
EmpEraturE
Ensor
onnECtions
Label
Function / Description
Show ambient temperatures (optional if weather feed is acceptable; use X2658
Outdoor Sensor - 2 terminals).
Outdoor Air
NOTE:
Wiring distance between the thermostat and the outdoor temperature
Sensor
sensor can not exceed 200 feet (61 m) when wired with 18AWG ther-
mostat wire.
Optional for diagnostics of indoor air; use 88K38 Discharge Air Sensor - 2 termi-
nals.
Discharge Air
NOTE:
Wiring distance between the furnace or air handler control module and
Sensor
the discharge air sensor should not exceed 10 feet (3 meters) when
wired with 18 #AWG thermostat wire.
7
Furnace Heat Stages
Heat Pump Stages
1
100%
1
1
100%
1
2
70%, 100%
3
2
70%, 100%
3
Table 6. Sensors
100%
100%
70%, 100%
70%, 100%