Table 10. Thermostat (HD Display) Parameters
Parameter
Description
Options are ON and OFF. Default is OFF. This allows a wider low and
high temperature. Normal range is 60 to 90°F (15.5 to 32.0°C). When
this parameter is set to ON, the range is 40 to 100°F (0.0 to 40°C). This
Wide Setpoint
feature can also be set through the user interface setting screen. From
the home screen go to menu > settings > heat & cool > wider set-
point range.
Table 11. Mag-Mount Parameters
Parameter
Description
This provides information on equipment type name, control hardware
About
revision, control software revision, control serial number and control
model number.

Add / Remove Equipment

This selection allows the installer to add or remove 24VAC controlled equipment
such as outdoor units, humidifiers and dehumidifiers.
Table 12. Utilities
Parameter
Description
Restart Smart
Restarts the Smart Hub.
Hub
Re-configure
Re-configure HVAC system.
System
Reset HVAC
Resets all HVAC equipment.
Equipment
Factory Reset
Resets thermostat to factory default settings.
Thermostat
Factory Reset
Resets Smart Hub parameters back to factory default.
Smart Hub
n
otiFiCations
This section will list active notifications and service alerts. Service alerts codes are
as follows:

Mag-Mount

Reset

Table 13. Service Alert Codes
Alert Code
Description
3000
Filter 1
3001
Filter 2
3002
Humidifier pad
3003
UV light
3004
Maintenance
3005
PureAir maintenance
4000
User Wi-Fi state change, disabled.
4001
Firmware download failed
4002
Image file download failed
t
Ests
Select Test to check for any of the applicable relays, inputs and 24VAC voltage:
Available function tests are (based on system configuration) - Blower, HP Heat - 1st
Stage, HP Heat - 2nd Stage, Cooling - 1st Stage, Cooling - 2nd Stage, Electric Heat
- 1st Stage, Humidification.
• Specific relays tested if applicable are W1, W2, W3, Y1, Y2, O, G, Humidification,
and Dehumidification (open or closed)
• Interlock relay (open or closed)
• Auto-start delay (on or off)
• Outdoor temperature
• Discharge air temperature
• Various inputs are on or off (i.e., Y1, Y2, O, W1, G).
• 24VAC voltage (range between 18 and 30VAC is acceptable)
By default all tests are selected, you may de-select or select all or individually
enabling or disabling each test by touching the individual test option on the screen.
Once your selections have been made, proceed by touching the start test button
along the bottom of the screen.
When a specific set of tests are completed the results will be displayed on the
screen next to the tested item. Touch continue to proceed to the next set of test
items. Once all tests are completed press done to return to the touch tests to run
screen. Touch the left arrow at the top left side of screen to return to the Dealer
Control Center. Maximum time in test mode is 30 minutes. Also defrost testing will
only be energized for 30 seconds.