Operating Guide ECL Comfort 210/296/310, application A230
5.9 Compensation 1
The desired flow temperature can be influenced by a compensation
temperature, measured by S1.
This application contains 2 compensation temperature limits:
Compensation 1 (Comp. 1) and Compensation 2 (Comp. 2).
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Compensation 1
Limit (compensation temp., 1. point)
Set the compensation temperature limit point 1.
See Appendix "Parameter ID overview"
When the compensation temperature measured by Sx falls below
or gets higher than the set value, the controller automatically
changes the desired flow / duct temperature. The influence is set
in 'Infl. - max.' and 'Infl. - min.' .
MENU > Settings > Compensation 1
Adapt. time (adaptation time)
Controls how fast the compensation / surface temperature influences the
desired flow / duct temperature.
See Appendix "Parameter ID overview"
OFF:
The control function is not influenced by the 'Adapt.
time' .
Minor
The desired flow / duct temperature is adapted quickly.
value:
Major
The desired flow / duct temperature is adapted slowly.
value:
Value: Set the adaptation time
VI.LG.H4.02
Influence
1x060
Compensation 1
1x061
The adaptation function can correct the desired flow / duct
temperature with max. 8 K.
Temp. Sx
© Danfoss | 2017.05 | 95