Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Return limit
DHW, ret. T limit
When an addressed slave is active in DHW-tank heating / charging, the
return temperature limitation in the master can be set.
Notes:
The master circuit must be set to react on the desired flow temperature
in the slave(s). See "Demand offset" (ID 11017).
The slave(s) must be set to send its / their desired flow temperature to
the master. See "Send desired T" (ID 1x500).
See Appendix "Parameter ID overview"
OFF:
No influence from slaves. The return temperature
limitation is related to settings in "Return limit".
Value: Return temperature limitation value when slave is in
DHW tank heating / charging operation.
MENU > Settings > Return limit
Limit (return temp. limitation)
Set the return temperature value you accept for the system.
See Appendix "Parameter ID overview"
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.' .
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Set the outdoor temperature value for the low return temperature limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1' .
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1' .
74 | © Danfoss | 2017.05
1x029
# 1 # = Master, example A266, address 15
# 2 # = Slave, example A237, address 9
# 3 # = Slave, example A367, address 6
Some examples of applications with DHW-tank heating / charging are:
A217, A237, A247, A367, A377
1x030
1x031
1x032
VI.LG.H4.02