Danfoss ECL Comfort 296 Operating Manual page 100

Application a230
Hide thumbs Also See for ECL Comfort 296:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Application
Demand offset
The desired flow temperature in the master circuit can be influenced by the
demand for a desired flow temperature in another controller (slave) or
another circuit.
The 'Demand offset' can compensate for heating or cooling losses between
master and slave controlled systems.
Circuit 1 is the master circuit in most applications.
See Appendix "Parameter ID overview"
*
heating applications: OFF / 1 . . . 20 K
cooling applications: - 20 . . . -1 K / OFF
**
heating applications: OFF
cooling applications: OFF
OFF:
The desired flow temperature is not influenced by the
demand of any other controller (slave) or circuit.
Value:
The desired flow temperature is increased (heating) or
decreased (cooling) by the set value in 'Demand offset' .
100 | © Danfoss | 2017.05
Heating application
1x017
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, master
=
# 3 #
Desired flow temperature, slave
Cooling application
=
X
Time
=
Y
Desired flow temperatures
=
# 1 #
Demand offset
=
# 2 #
Desired flow temperature, slave
=
# 3 #
Desired flow temperature, master
Heating applications:
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest heating / DHW limitation
value.
VI.LG.H4.02