Danfoss ECL Comfort 296 Operating Manual page 107

Application a230
Hide thumbs Also See for ECL Comfort 296:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Application
Send desired T
When the controller acts as a slave controller in a master / slave system,
information about the desired flow temperature can be sent to the master
controller via the ECL 485 bus.
Stand-alone controller:
Sub-circuits can send the desired flow temperature to the master circuit.
See Appendix "Parameter ID overview"
OFF:
Information about the desired flow temperature is not
sent to the master controller.
ON:
Information about the desired flow temperature is sent
to the master controller.
VI.LG.H4.02
1x500
In the master controller, 'Demand offset' must be set to a value in order
to react on a desired flow temperature from a slave controller.
When the controller acts as a slave, its address must be 1, 2, 3 ... 9 in
order to send the desired temperature to the master (see the section
'Miscellaneous' , 'Several controllers in the same system').
© Danfoss | 2017.05 | 107