Advertisement

Operating Guide ECL Comfort 210/296/310, application A230
Maximum load ratings:
Relay terminals
Triac (= electronic
relay) terminals
A230.2 (cooling): 2-pump control
Application A230.2, ex. d is an example for scheduled shift between
two circulation pumps.
Control of P1 is based on the cooling demand and determines
via K1 the ON / OFF control of the pumps P2 and P3. P2 and P3
are related to the output of the schedule in "Common controller
settings".
The electric diagram for A230.2, P2 and P3 shows an example for
connection.
18 | © Danfoss | 2017.05
4 (2) A / 230 V a.c.
(4 A for ohmic load, 2 A for
inductive load)
0,2 A / 230 V a.c.
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
VI.LG.H4.02