Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Compensation 2
Infl. - min. (compensation temp., 2. point)
Circuit
Determines how much the desired flow / duct temperature will be influenced
if the compensation temperature is lower than the set limit.
See Appendix "Parameter ID overview"
Influence higher than 0:
The desired flow / duct temperature is increased, when the
compensation temperature gets below the set limit.
Influence lower than 0:
The desired flow / duct temperature is decreased, when the
compensation temperature gets below the set limit.
98 | © Danfoss | 2017.05
1x067
Setting range
Factory setting
Example
The limit value is set to 25 °C.
'Infl. min. ' is set to 0.5.
The actual compensation temperature is 23 °C (2 degrees below the
limit value).
Result:
The desired flow / duct temperature is changed by 0.5 x 2= 1.0 degree.
VI.LG.H4.02