Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Flow temperature
Desired T (Desired flow temperature)
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim. '
See Appendix "Parameter ID overview"
MENU > Settings > Flow temperature
Des. T Comfort
Setting of desired flow temperature when the ECL controller is in comfort
mode.
See Appendix "Parameter ID overview"
MENU > Settings > Flow temperature
Des. T Saving
Setting of desired flow temperature when the ECL controller is in saving
mode.
See Appendix "Parameter ID overview"
MENU > Settings > Flow temperature
Ext. signal
See Appendix "Parameter ID overview"
OFF:
The desired flow temperature is set in the controller.
ON:
The desired flow temperature is applied as a 0 - 10 V
signal.
66 | © Danfoss | 2017.05
1x004
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
The "Desired T" value can be influenced by:
•
temp. max.
•
temp. min.
•
room temp. limit
•
return temp. limit
•
flow / power limit
1x018
This setting has no influence if the controller receives an external value
for the desired flow temperature.
1x019
This setting has no influence if the controller receives an external value
for the desired flow temperature.
1x084
See 'Ext. desired T' . The value is an externally set desired flow
temperature.