Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Flow temperature
Temp. min.
See Appendix "Parameter ID overview"
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
MENU > Settings > Flow temperature
Temp. max.
See Appendix "Parameter ID overview"
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
VI.LG.H4.02
1x177
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
1x178
The setting of 'heat curve' is possible for heating circuits only.
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .