Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Application
P demand
The circulation pump in the master circuit can be controlled in relation to
the master circuit's demand or slave circuit's demand.
See Appendix "Parameter ID overview"
Heating applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the heating circuit is higher than the
value set in 'P heat T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is higher than the value set in
'P heat T' .
Cooling applications:
OFF:
The circulation pump is ON when the desired flow
temperature in the cooling circuit is lower than the value
set in 'P cool T' .
ON:
The circulation pump is ON when the desired flow
temperature from slaves is lower than the value set in
'P cool T' .
MENU > Settings > Application
DHW priority (closed valve / normal operation)
The heating circuit can be closed when the controller acts as slave and when
DHW heating / charging is active in the master.
See Appendix "Parameter ID overview"
OFF:
The flow temperature control remains unchanged
during active DHW heating / charging in the master
controller.
ON:
The valve in the heating circuit is closed* during active
DHW heating / charging in the master controller.
* The desired flow temperature is set to the value set in
'Frost pr. T'
MENU > Settings > Application
P cool T (cooling demand)
When the desired flow temperature is below the set temperature in 'P cool T' ,
the controller automatically switches ON the circulation pump.
See Appendix "Parameter ID overview"
Value: The circulation pump is switched ON when the desired
flow temperature is below the set value.
102 | © Danfoss | 2017.05
1x050
The circulation pump is always controlled according to frost protection
conditions.
1x052
This setting must be considered if this controller is a slave.
1x070
The valve is fully closed as long as the pump is not switched on.