Operating Guide ECL Comfort 210/296/310, application A230
A230, in general (continued):
Commissioning
When the A230 application has been uploaded the ECL Comfort
controller starts in Manual mode. This can be used to verify correct
connections of temperature, pressure and flow sensors. Also
verifying the controlled components for correct functionality can
be done.
Depending on system type, it might be necessary to change some
factory settings individually in order to optimize the functionality.
The application key must be inserted in order to change settings.
Important:
Set the correct running time "M run" of the Motorized Control
Valve M1. (Circuit 1 > MENU > Settings > Control parameters
> M run).
VI.LG.H4.02
The controller is pre-programmed with factory settings that are shown
in the 'Parameter ID overview' appendix.