Danfoss ECL Comfort 296 Operating Manual page 73

Application a230
Hide thumbs Also See for ECL Comfort 296:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A230
Example, minimum return temperature limitation;
return temperature gets lower than limit
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Return limit
Con.T, re. T lim. (Constant temperature mode, return
temperature limitation)
The "Con. T, ret. T limit" is the return temperature limitation value when the
circuit is set to override mode type "Const. T" (= Constant temperature).
See Appendix "Parameter ID overview"
Value: Set the return temperature limitation
VI.LG.H4.02
= Temperature
T
= Temperature
Y
= Time
X
# 1 # = Return temperature
# 2 # = Return temperature limit
# 3 # = Desired flow temperature
# 4 # = Action point
1x028
© Danfoss | 2017.05 | 73