Danfoss ECL Comfort 296 Operating Manual page 113

Application a230
Hide thumbs Also See for ECL Comfort 296:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210/296/310, application A230
MENU > Settings > Alarm
Alarm low
When the measured value gets lower than the set value, the alarm will be
activated.
See Appendix "Parameter ID overview"
Value:
Set the alarm value
MENU > Settings > Alarm
Alarm time-out
The alarm is activated when the alarm reason has been present for a longer
time (in seconds) than the set value.
See Appendix "Parameter ID overview"
Value:
Set the alarm time-out
MENU > Settings > Alarm
Upper difference
The alarm is activated if the actual flow / duct temperature increases more
than the set difference (acceptable temperature difference above the desired
flow / duct temperature). See also 'Delay' .
See Appendix "Parameter ID overview"
OFF:
The related alarm function is not active.
Value:
The alarm function is active if the actual temperature
gets above the acceptable difference.
VI.LG.H4.02
1x615
1x617
Upper difference
1x147
=
X
Time
=
Y
Temperature
=
# 1 #
Upper difference
=
# 2 #
Desired flow temperature
© Danfoss | 2017.05 | 113

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecl comfort 210Ecl comfort 310

Table of Contents