Fortigate-5060 Chassis Back Panel - Fortinet FortiGate-5060 Chassis Manual

Hide thumbs Also See for FortiGate-5060:
Table of Contents

Advertisement

FortiGate-5060 chassis

FortiGate-5060 chassis back panel

FortiGate-5060 Chassis Guide
01-400-129494-20110912
http://docs.fortinet.com/
Feedback
Figure 2
shows the back of a FortiGate-5060 chassis. The FortiGate-5060 chassis back
panel includes two redundant -48V to - 60 VDC power entry modules (PEMs) labelled
PEM A and PEM B. Fortinet ships the FortiGate-5060 chassis with PEM A and B installed.
The PEMs provide redundant DC power connections for the FortiGate-5060 chassis and
distribute DC power to the chassis slots and to the fan trays.
If you require redundant power you should connect both PEMs to DC power. If redundant
power is not required, you can connect PEM A or PEM B. Each PEM includes two power
terminals, one for connecting to -48V/-60 VDC and one for connecting to RTN. Use two-
hole lugs to connect the power terminals to DC power.
to connect PEM B to a DC power source.
Figure 2: FortiGate-5060 chassis back panel (shows PEM B connected to DC power source)
-48V/-60 VDC
nom (black)
(lower)
Power
Entry Module
(PEM) B
Branch 1
PEM
PEM B
ESD
socket
Chassis
Ground
Connector
(green)
The back panel includes the FortiGate-5060 chassis ground connector which must be
connected to Data Center ground. The FortiGate-5060 chassis also includes an ESD
socket on the back panel.
For detailed information about connecting power to the FortiGate-5060 chassis, see
"Connecting the FortiGate-5060 chassis to DC power and data center ground" on page 17
or
"Connecting the FortiGate-5060 chassis to AC power using a FortiGate power
converter shelf" on page
The back panel also contains 6 RTM slots numbered to correspond to the front panel
slots. The RTM slots are available for FortiGate-5000 RTM modules such as the
FortiGate-RTM-XB2 module or the FortiGate-RTM-XD2 module. When the
FortiGate-5060 chassis is shipped, these slots are covered by RTM air baffle slot covers.
RTN
(red)
Entry Module
(upper)
(PEM) A
Branch 2
Branch 1
RTN
-48/-60 V
PEM
RTM Air Baffle slot covers
20.
FortiGate-5060 chassis back panel
Figure 2
shows the wiring required
Power
Branch 2
RTN
-48/-60 V
PEM A
9

Advertisement

Table of Contents
loading

Table of Contents