Shelf Alarm Panel Telco Alarms - Fortinet FortiGate-5060 Chassis Manual

Hide thumbs Also See for FortiGate-5060:
Table of Contents

Advertisement

FortiGate-5060 shelf alarm panel

Shelf alarm panel telco alarms

14
Figure 5: Connections between the shelf managers and the shelf alarm panel
5000SAP
SERIAL
1
I²C-Switch
PCA9545
ShMM-500
Secondary Shelf Manager (Left)
The shelf alarm panel telco alarm interface relay circuits are capable of carrying 60 VDC
or 1 A with a max. rating of 30 VA. The shelf alarm panel accepts timed pulse inputs for
clearing minor and major alarm states. Reset is accomplished by asserting a voltage
differential from 3.3 V to 48 V for between 200 and 300 ms. The acceptance voltage range
is from 0 to 48 VDC continuous (handles up to 60 VDC at a 50% duty cycle). The current
drawn by a reset input does not exceed 12 mA.
The alarm LED reset button activates the alarm cutoff (ACO) state for major, minor, and
user-defined alarms. You cannot reset critical alarms with the alarm LED reset button.
When the ACO state is activated, active alarm LEDs blink and all of the alarm relays are
deactivated. The alarm reset button activates the ACO state but does not clear the alarm
completely.
Figure 6: The telco alarm connector (DB-15 male)
15
8
RESET
Buffer
I²C-Switch
LTC4300
PCA9545
ShMM-500
Primary Shelf Manager (Right)
9
1
FortiGate-5060 chassis
SERIAL
2
Buffer
LTC4300
FortiGate-5060 Chassis Guide
01-400-129494-20110912
http://docs.fortinet.com/
Feedback