Electrical Service
All wiring must conform to local, state and national
codes.
VOLTAGE
The maximum allowable voltage variation is ± 10% of the
rated voltage on the ice machine model/serial number
plate at compressor start-up.
FUSE/CIRCUIT BREAKER
A separate fuse/circuit breaker must be provided for each
ice machine. Circuit breakers must be H.A.C.R. rated (does
not apply in Canada).
The ice machine must be grounded in accordance with
national and local electrical codes.
GROUND FAULT INTERRUPTER CIRCUIT (GFIC)
A GFCI/GFI circuit protection is not recommended with
our equipment. If a GFCI/GFI is required by code a GFCI/
GFI breaker rather than outlet must be used to avoid
intermittent nuisance trips.
Part Number 000007661 11/16