Input Equipment Service Parameters If Necessary; Verify Vfd Configuration And Change; Parameters If Necessary; Vfd Chiller Field Set Up And Verification - Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

PARAMETER
Motor Nameplate Voltage
Compressor 100% Speed
Line Freq=60 Hz? (No=50)
Rated Line Voltage
Rated Line Amps
Rated Line Kilowatts
Motor Rated Load KW
Motor Rated Load Amps
Motor Nameplate Amps
Motor Nameplate RPM
Motor Nameplate KW
Surge Limit/HGBP Option
Minimum Load Points (Tsmin, IGVmin)
FULL (Maximum) load points (TsMax, IGVmax)
Surge Line Shape Factor
Chilled Medium
Evaporator Refrigerant trippoint
*Evaporator Flow Delta P cutout
Condenser Flow Delta P cutout
High Condenser Water Delta P
Diffuser Option (compressors with Split Ring Diffusers)
Diffuser Full Span mA (Compressors with Split Ring
Diffusers)
*With variable flow systems this point may be configured to the lower
end of the range.
INPUT EQUIPMENT SERVICE PARAMETERS IF NEC-
ESSARY — The EQUIPMENT SERVICE table has six
service tables.

VERIFY VFD CONFIGURATION AND CHANGE

PARAMETERS IF NECESSARY (Fig. 40)
IMPORTANT: The VFD controller has been factory config-
ured for use and communications to the International Chiller
Visual Controller (ICVC). Some parameters are specific to
the chiller configuration and will need to be verified prior to
operation. All command functions must be initiated from
the ICVC.

VFD CHILLER FIELD SET UP AND VERIFICATION

Label Locations — Verify that the following labels have been
installed properly and match the chiller requisition:
• Surge Parameters — Located inside the control panel. See
Fig. 14.
• Refrigeration Machine Nameplate — Located on the right
side of the control panel. See Fig. 14.
• External Machine Electrical Data Nameplate — Located on
the right side of the VFD as viewed from its front. See
Fig. 40.
• Internal Machine Electrical Data Nameplate — Located on
the inside of the left VFD enclosure door. See Fig. 40.
• Record all nameplate information on the Initial Start-up
Checklist at the end of this manual.
Table 13 — Job Site Parameters
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
VFD_CONF - from chiller information nameplate
OPTIONS - Enter 1 or 2 if HGBP is installed. Enter 0 otherwise.
OPTIONS - Per Chiller Requisition (Tsmin, IGVmin) per job data - See Modify
Load Points section. Refer to table located in the control panel.
OPTIONS - Per Chiller Requisition (Tsmax, IGVmax) per job data - See Modify
Load Points section. Refer to table located in the control panel.
OPTIONS - Per Chiller Requisition. Refer to table located in the control panel.
SETUP1 - Enter Water or Brine
SETUP1 - Usually 3 F (1.7 C) below design refrigerant temperature
SETUP1 - Per Chiller Requisition if available or enter 50% of design pressure
drop
SETUP1 - Per Chiller Requisition if available or enter 50% of design pressure
drop
Enter the maximum value for the condenser water pressure drop if chiller is
connected to a condenser water manifold system. Otherwise leave at default.
SETUP2 - ENABLE for 4 and 5 frame compressors with Split Ring Diffusers.
See table in control panel for values.
SETUP2 - Enter diffuser actuator full span mA value for 4 and 5 frame compres-
sors with Split Ring Diffusers. See label on side of diffuser actuator for values.
NOTE: Other parameters: Screens are normally left at the default
settings; they may be changed by the operator as required. The time
and persistence settings on the VFD_CONF table can be adjusted
to increase or decrease the sensitivity to a fault condition. Increasing
time or persistence decreases sensitivity. Decreasing time or per-
sistence increases sensitivity to the fault.
74
TABLE
INTERNAL
Fig. 40 — Machine Electrical Data Nameplate
EXTERNAL
a19-1626