Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 106

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

J. CHILLER ALERTS (cont)
ICVC
PRIMARY
FAULT
MESSAGE
STATE
167
SYSTEM ALERT
168
SENSOR ALERT
AUTORESTART
169
PENDING
AUTORESTART
170
PENDING
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 16 — Alarm and Alert Messages (cont)
SECONDARY
MESSAGE
HIGH DISCHARGE TEMP 167Comp Discharge Temp
[VALUE] exceeded limit of
[LIMIT]*.
HUMIDITY SENSOR
168Sensor Fault: Check
INPUT
Humidity Sensor Input Sen-
sor.
VFD COMMUNICATIONS
169Loss of SIO Comm with
FAULT
VFD Gateway; Check VFG
Module and Power.
VFD COMMUNICATIONS
170Loss of DPI Comm with
FAULT
VFD Gateway; Check VFG to
VFD Comm.
PRIMARY CAUSE
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for excessive starts.
Check Comp Discharge Alert setting in SETUP1
screen.
Check humidity sensor wiring on CCM connec-
tors J3 and J5. CCM switch SW2-1 must be in
"OFF" position.
Check Humidity Sensor Input in Controls Test.
The communication between the VFD Gateway
and the CCM board is not occurring. Check wir-
ing at CCM, in the power panel (Terminals
A,B,C). Check wiring from Power panel to VFD.
The communication between the VFD Gateway
and the DPI is not occurring. Check ribbon cable
between the two components, power to the DPI
card.
106
ADDITIONAL CAUSE/REMEDY