Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 101

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

I. CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC
PRIMARY
FAULT
MESSAGE
STATE
220
PROTECTIVE LIMIT
221
PROTECTIVE LIMIT UNUSED
222
PROTECTIVE LIMIT
LOSS OF
223
COMMUNICATION
224
PROTECTIVE LIMIT
225
PROTECTIVE LIMIT
PROTECTIVE LIMIT LINE PHASE REVERSAL
226
227
PROTECTIVE LIMIT
228
PROTECTIVE LIMIT
229
PROTECTIVE LIMIT
230
PROTECTIVE LIMIT
231
PROTECTIVE LIMIT
232
PROTECTIVE LIMIT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 16 — Alarm and Alert Messaged (cont)
SECONDARY
MESSAGE
GROUND FAULT
220Ground Fault Trip;
Check Motor and Current
Sensors.
221UNUSED
LINE FREQUENCY TRIP
222Line Frequency —
[VALUE] exceeded limit of
[LIMIT]; Check Power Supply.
WITH VFD GATEWAY
223Loss of SIO Comm with
MODULE
VFD Gateway: Check VFG
Module and Power.
VFD COMMUNICATIONS
224Loss of DPI Comm with
FAULT
VFD Gateway: Check VFG to
VFD Comm.
MOTOR CURRENT
225Motor Current Imbal-
IMBALANCE
ance: Check VFD Fault
History for Values.
226Line Phase Reversal:
Check Line Phases.
OIL PRESS SENSOR
227Oil Pressure Delta P
FAULT
[VALUE] (Pump Off): Check
Pump/Transducers.
LOW OIL PRESSURE
228Low Operating Oil
Pressure [VALUE]: Check Oil
Pump and Filter.
LOW CHILLED WATER
229Low Chilled Water Flow;
FLOW
Check Switch/Delta P Config
& Calibration.
LOW CONDENSER
230Low Condenser Water
WATER FLOW
Flow; Check Switch/Delta P
Config & Calibration.
HIGH DISCHARGE TEMP 231Comp Discharge Temp
[VALUE] Exceeded Limit of
[LIMIT]*.
LOW REFRIGERANT
232Evaporator Refrig Temp
TEMP
[VALUE] exceeded limit of
[LIMIT]*.
PRIMARY CAUSE
Check for condensation on motor terminals.
Check motor power leads for phase to phase or
phase to ground shorts. Disconnect motor from
VFD and megger motor.
Call Carrier Service.
If operating from a generator, check generator
size and speed.
Check utility power supply.
Check VFD communication wiring and
connectors on VFD Gateway and DPI board.
Check for compatibility between ICVC and
Gateway software.
Check VFD communication wiring and
connectors.
Check status lights on DPI Communications
Interface Board.
Call Carrier Service.
Check Motor Current % Imbalance in VFD_-
CONF screen.
Reverse connections of any two line conductors
to circuit breaker.
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check transducer calibration.
Check transducer wiring and accuracy.
Check power supply to pump.
Check pump operation.
Check oil level.
Check for partially closed service valves.
Check oil filters.
Check for foaming oil at start-up.
Check transducer calibration.
Perform pump control test.
Check optional transducer calibration and
wiring.
Check Evaporator Refrigerant Temperature
sensor.
Check chilled water valves.
Check for evaporator saturation temperature
< 34 F if not in Pumpdown Lockout mode. Place
unit in Pumpdown mode before removing
charge.
Perform pump control test.
Check optional transducer calibration and
wiring.
Check condenser water valves.
Check for condenser pressure > 130 PSIG.
Check for closed compressor discharge isola-
tion valve.
Check if chiller was operating in surge.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper condenser flow and
temperature.
Check compressor discharge isolation valve.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper refrigerant charge.
Check float valve operation.
Check for closed condenser liquid line isolation
valve. If problem occurs at high load, check for
low condenser pressure which causes inade-
quate FLASC orifice differential pressure.
Check for proper water flow and temperature.
Confirm that condenser water enters bottom row
of condenser tubes first.
Check Evaporator Refrigerant Temperature
sensor.
Check for division plate gasket bypass.
Check for fouled tubes.
101
ADDITIONAL CAUSE/REMEDY