F. NORMAL RUN
PRIMARY MESSAGE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — RESET ACTIVE
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
RUNNING — DEMAND LIMITED
RUNNING — DEMAND LIMITED
RUNNING — TEMP CONTROL
G. NORMAL RUN WITH OVERRIDES
ICVC
PRIMARY
FAULT
MESSAGE
STATE
RUN CAPACITY
120
LIMITED
RUN CAPACITY
121
LIMITED
RUN CAPACITY
122
LIMITED
RUN CAPACITY
123
LIMITED
RUN CAPACITY
124
LIMITED
RUN CAPACITY
125
LIMITED
RUN CAPACITY
126
LIMITED
RUN CAPACITY
127
LIMITED
RUN CAPACITY
128
LIMITED
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 16 — Alarm and Alert Messages (cont)
SECONDARY MESSAGE
BY 4-20 mA SIGNAL
REMOTE TEMP SENSOR
CHW TEMP DIFFERENCE
LEAVING CHILLED WATER
ENTERING CHILLED WATER
TEMPERATURE RAMP LOADING
BY DEMAND RAMP LOADING
BY LOCAL DEMAND SETPOINT
BY 4-20 mA SIGNAL
BY CCN SIGNAL
BY LOADSHED/REDLINE
HOT GAS BYPASS
BY LOCAL SIGNAL
ICE BUILD MODE
MOTOR LOAD CURRENT
VFD LINE CURRENT
IN VFD RAMPDOWN
SECONDARY
PRIMARY CAUSE
MESSAGE
HIGH CONDENSER
120Condenser Pressure
PRESSURE
[VALUE] exceeded limit of
[LIMIT]*.
HIGH MOTOR
121Comp Motor Winding
TEMPERATURE
Temp [VALUE] exceeded
limit of [LIMIT]*.
LOW EVAP REFRIG
122Evaporator Refrig
TEMP
Temp [VALUE] exceeded
limit of [LIMIT]*.
HIGH COMPRES-
123Surge Prevention
SOR LIFT
Override: Lift Too High For
Compressor
MANUAL GUIDE
124Run Capacity Limited:
VANE
Manual Guide Vane Target.
TARGET
LOW DISCHARGE
No Alert message.
SUPERHEAT
HIGH RECTIFIER
126Rectifier Temperature
TEMP
[VALUE] exceeded limit of
[LIMIT]*.
MANUAL SPEED
No Alert message.
CONTROL
HIGH INVERTER
128Inverter Temperature
TEMP
[VALUE] exceeded limit of
[LIMIT]*.
CAUSE/REMEDY
Auto chilled water reset active based on external input.
Auto chilled water reset active based on external input.
Auto chilled water reset active based on CHW Delta T in
TEMP_CTL screen.
Default method of temperature control.
Entering Chilled Water control enabled in TEMP_CTL screen.
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Ramp Loading in effect. Use RAMP_DEM screen to modify.
Demand limit set point is less than actual demand.
Demand limit is active based on external auto demand limit option.
Demand limit is active based on control limit signal from CCN.
Demand limit is active based on LOADSHED screen set-up.
Hot gas bypass valve is energized (open). See Surge prevention
description.
Active demand limit manually overridden on MAINSTAT table.
Chiller is running under Ice Build temperature control.
Chiller has reached 100% of Load Current Rating during normal
operation.
Chiller has reached 100% of Line Current Rating during normal
operation.
Post-start-up, speed reducing, and guide vanes opening to reach
normal operating state.
Check condenser water pump operation.
Check for high condenser water temperatures or
low flow rate. Verify that isolation valves are open.
Check Cond Press Override setting in SETUP1.
Check for closed valves or restriction in motor cool-
ing lines.
Check for closed refrigerant isolation valves.
Check Comp Motor Temp Override setting in SET-
UP1.
Check refrigerant charge.
Check that optional cooler liquid line isolation valve
is fully open.
Check for excessive condenser flow or low chilled
water flow.
Check for low entering cooler temperature.
Check that condenser inlet and outlet water
nozzles are piped correctly.
Check for waterbox division plate gasket bypass.
Check for high condenser water temperature or low
suction temperature.
Check for high Evaporator or Condenser
approaches.
Check surge prevention parameters in OPTIONS
screen.
Target Guide Vane Position has been forced in the
COMPRESS screen. Select and RELEASE force to
return to normal (automatic) operation.
Check for oil loss or excess refrigerant charge. Ver-
ify that the valves in the oil reclaim lines are open.
Check Rectifier Temp Override in SETUP1 screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
Chiller is not in automatic temperature control.
Check Inverter Temp Override in SETUP1 screen.
Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling solenoid.
Check for proper VFD cooling fan operation and
blockage.
98
ADDITIONAL CAUSE/REMEDY