Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 104

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

I. CHILLER PROTECTIVE LIMIT FAULTS (cont)
ICVC FAULT
PRIMARY
STATE
MESSAGE
259
PROTECTIVE LIMIT
282
PROTECTIVE LIMIT
283
PROTECTIVE LIMIT
284
VFD GATEWAY
285
VFD GATEWAY
286
PROTECTIVE LIMIT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm
condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
J. CHILLER ALERTS
ICVC FAULT
PRIMARY
STATE
MESSAGE
140
SENSOR ALERT
141
SENSOR ALERT
LOW OIL
142
PRESSURE ALERT
AUTORESTART
143
PENDING
AUTORESTART
144
PENDING
AUTORESTART
145
PENDING
AUTORESTART
146
PENDING
AUTORESTART
147
PENDING
AUTORESTART
148
PENDING
149
MACHINE ALERT
150
SENSOR ALERT
*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm
condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.
Table 16 — Alarm and Alert Messages (cont)
SECONDARY
PRIMARY CAUSE
MESSAGE
CCN OVERRIDE
259CCN Emergency/
STOP
Override Stop.
INVALID VFD CON-
282Line Frequency
FIG
[VALUE] Exceeded Configura-
tion Range.
INVALID VFD CON-
283Compressor 100%
FIG
Speed Config Ranges: 50=Hz
45-52; 60 Hz=55-62.
COMPATIBILITY
284VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/VFD
Versions.
COMPATIBILITY
285VFD Gateway Compati-
CONFLICT
bility Conflict: Check VFG/
ICVC Versions.
INVERTER
286Inverter Overcurrent
OVERCURRENT
Fault: Check VFD Status.
SECONDARY
PRIMARY CAUSE
MESSAGE
LEAVING COND
140Sensor Fault: Check
WATER TEMP
Leaving Cond Water Sensor.
ENTERING COND
141Sensor Fault: Check
WATER TEMP
Entering Cond Water Sensor.
CHECK OIL FILTER
142Low Oil Pressure Alert.
Check Oil Filter.
LINE CURRENT
143Line Current Imbalance:
IMBALANCE
Check VFD Fault History for
Values.
LINE VOLTAGE
144Single Cycle Line
DROP OUT
Voltage Dropout.
HIGH LINE VOLT-
145High Percent Line
AGE
Voltage [VALUE].
LOW LINE VOLTAGE 146Low Percent Line
Voltage [VALUE].
VFD MODULE
147VFD Module Power-On
RESET
Reset When Running.
POWER LOSS
148Control Power-Loss
When Running.
HIGH COND WATER
149High Flow: Condenser
FLOW
Water Delta P [VALUE]
Exceeded Limit of [LIMIT]*.
HIGH BEARING
150Comp Thrust Brg Temp
TEMPERATURE
[VALUE] exceeded limit of
[LIMIT]*.
CCN has signaled the chiller to stop.This fault must be
manually reset from the default screen of the ICVC.
LINE FREQUENCY in POWER screen must be main-
tained between 45-52 Hz if LINE FREQ=60Hz? is set to
NO(50 Hz). LINE FREQUENCY must be maintained
between 55-62 Hz if LINE FREQ=60Hz? is set to YES
(60 Hz).
Check 2C AUX/HPR Gate Kill circuit.
COMPRESSOR 100% SPEED in VFD_CONF screen
must be set between 45-52 Hz if LINE FREQ=60Hz? is
set to NO (50 Hz). COMPRESSOR 100% SPEED must
be set between 55-62 Hz if LINE FREQ=60Hz? is set to
YES (60 Hz).
VFD Gateway and VFD software versions are not com-
patible.
Call Carrier Service.
VFD Gateway and ICVC software versions are not com-
patible.
Call Carrier Service.
Check for high entering water temperature or low con-
denser water flow.
Check current settings in VFD_CONF screen.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.
Power loss has been detected in any phase.
Chiller automatically restarting.
A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically restarting if Auto Restart is enabled
in SETUP3 screen.
Check phase to phase and phase to ground line power.
Check phase to phase and phase to ground line power.
VFD Module has detected a hardware fault due to elec-
trical noise, power loss or software and has reset.
Chiller automatically restarting.
Check for power loss and sources of electromagnetic
interference.
Check 24 vac control power supply to ICVC.
COND HI FLOW ALARM OPT is disabled and CON-
DENSER WATER DELTA P has exceeded configured
limit. Check FLOW DELTA P DISPLAY and COND HI
FLOW DEL P LIMIT in SETUP1 screen. Check optional
condenser water pressure transducer wiring and accu-
racy. Confirm that 5 V reference signal is available
between CCM J3-19 and J3-21 and J3-22 and J3-24.
Check for disconnected, grounded, or shorted wiring. If
pressure transducers are not installed, check for pres-
ence of resistors and jumpers CCM terminals J3-19
through J3-24. See Chiller Controls Schematic if flow
switches are used.
Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil temperature.
104
ADDITIONAL CAUSE/REMEDY
ADDITIONAL CAUSE/REMEDY