Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 192

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Base Demand Limit
LCW Setpoint
ECW Setpoint
Ice Build Setpoint
Tower Fan High Setpoint
Upload all control configuration tables via service tool?
ICVC Software
Part Number (See ICVC Configuration Screen)
ICVC Controller Identification
VFD Gateway Version Number (See VFD_STAT Screen):
VFD Inverter Version Number (See VFD_STAT Screen):
VFD Rectifier Version Number (See VFD_STAT Screen):
19XRV PIC III SETPOINT TABLE CONFIGURATION SHEET
RANGE
40 to 100
10 to 120
(-12.2 to 48.9)
15 to 120
(-9.4 to 48.9)
15 to 60
(-9.4 to 15.6)
55 to 105
(13 to 41)
(See ICVC Configuration Screen)
UNITS
DEFAULT
%
100
DEG F (C)
50.0 (10)
DEG F (C)
60.0 (15.6)
DEG F (C)
40.0 (4.4)
DEG F (C)
75 (24)
Yes
No
:
: BUS:
CCN ADDRESS:
CL-4
VALUE