Table 17 — Fault Code Descriptions and Corrective Actions (cont)
Fault Type indicates if the fault is:
1 — Auto-resettable
2 — Non-resettable
3 — User-configurable
4 — Normal Fault
VFD FAULT
FAULT TYPE
CODE
Incompat MCB-PB 2 Drive rating information stored on the
106
Replaced MCB-PB 2 Main Control board was replaced and
107
I/O Board Mismatch
120
4
I/O Board Comm
121
Loss 2
I/O Board Fail
122
200
Inverter Dsat
U, V, W
201
202
203
Inverter
OverCurrent
204
U, V, W
205
Inverter Unused Bit 4 Inverter section of power structure hard-
206
207
Invtr Gate Kill
208
Rectifier Dsat
R, S, T
209
210
211
Rectifier IOC
R, S, T
212
213
Reactor Temp
214
Rectifier HW Unused
215
4
Rectifier Ground
216
Fault
Rectifier Base Temp Excessive rectifier temperature
217
Rectifier IGBT Temp Excessive calculated IGBT temperature.
218
Rectifier IT
219
Overload
Rectifier I2T
220
Overload
Ride Thru Abort
221
High AC Line
222
223
Low DC Bus
Rctfr Over Volt
224
LEGEND
DPI
— Drive Peripheral Interface
EPROM — Erasable, Programmable, Read-Only
FLA
— Full Load Amps
IGBT
— Insulated Gate Bipolar Transistor
I/O
— Inputs/Outputs
NP
— Nameplate
NOTE: Reliance parameter numbers are indicated by ( ).
DESCRIPTION
power board is incompatible with the Main
Control board.
parameters were not programmed.
Incorrect I/O board identified.
Loss of communication to I/O board.
Board failure.
High current was detected in an IGBT.
High current was detected in an IGBT.
ware reported unexpected fault.
Inverter gate kill contact is open.
High current was detected in an IGBT.
Rectifier overcurrent.
Temperature switch in reactor opened.
Rectifier section of power structure hard-
ware reported unexpected fault.
Excessive ground current measured.
measured.
Short-term current rating of rectifier
exceeded.
Long-term current rating of rectifier
exceeded.
Input power loss timed out.
Input line voltage is too high.
The bus voltage is too low.
The bus voltage is too high.
ACTION
Load compatible version files into drive.
a. Press reset.
b. Reprogram parameters.
Restore I/O board to original configuration, or,
if new configuration is desired, reset fault.
Cycle power.
a. Cycle power.
b. If fault repeats, replace I/O board.
a. Check for loose connection in IGBT wire
harness.
b. Check IGBTs.
c. Check precharge resistors and fuses.
d. Check precharge contactor.
a. Verify proper motor data is entered.
b. Reduce current limit.
Check wiring harness.
Close gate kill contact.
a. Check for loose connection in IGBT wire
harness.
b. Check IGBTs.
a. Verify proper motor data is entered.
b. Reduce current limit.
Check for proper temperature and fan
operation.
Check wiring harness.
Check for grounded input wiring.
Check for proper temperature and flow rate of
coolant.
Check for proper temperature and flow rate of
coolant.
Low input voltage can result in increased cur-
rent load. Provide proper input voltage to the
drive.
Low input voltage can result in increased cur-
rent load. Provide proper input voltage to the
drive.
a. Verify input power and connections.
b. Check Line Sync board.
c. Check AC Line I/O board.
Reduce input voltage to meet specification of
480 ±10%.
Verify proper input voltage.
Monitor the AC line for high line voltage or
transient conditions. Bus overvoltage can also
be caused by motor regeneration. Extend the
decel time or install dynamic brake option.
109
ICVC FAULT
STATE
206
206
206
206
206
201
286
206
207, 235
200
241
206
206
220
218
218
212
212
210
211
215
205