Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 198

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Lead Lag Control
LEAD/LAG: Configuration
DSABLE=0, LEAD=1,
LAG=2, STANDBY=3
Load Balance Option
Common Sensor Option
LAG% Capacity
LAG Address
LAG START Timer
LAG STOP Timer
PRESTART FAULT Timer
PULLDOWN Timer
STANDBY Chiller Option
STANDBY% Capacity
STANDBY Address
DESCRIPTION
Pulldown Ramp Type:
Select: Temp=0, Load=1
Demand Limit and kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
Amps or kW Load Ramp% Min
Demand Limit Prop Band
Demand Limit At 20 mA
20 mA Demand Limit Opt
VFD Overload Decrease
VFD Overload Delta
Demand Watts Interval
19XRV PIC III LEADLAG TABLE CONFIGURATION SHEET
RANGE
0 to 3
0/1
DSABLE/ENABLE
0/1
DSABLE/ENABLE
25 to 75
%
1 to 236
2 to 60
MIN
2 to 60
MIN
2 to 30
MIN
1 to 30
MIN
0/1
DSABLE/ENABLE
25 to 75
%
1 to 236
19XRV PIC III RAMP_DEM TABLE CONFIGURATION SHEET
RANGE
0/1
0/1
5 to 20
3 to 15
40 to 100
0/1
25 to 50
3 to 15
5 to 60
UNITS
POINT
leadlag
loadbal
commsens
lag_per
lag_add
lagstart
lagstop
preflt
pulldown
stndopt
stnd_per
stnd_add
UNITS
POINT
ramps1ct
dem_src
kw_ramp
%
dem_app
%
dem_20ma
DSABLE/
dem_sel
ENABLE
%
vfd_dec
%
vfd_delt
MIN
dw_int
CL-10
DEFAULT
VALUE
0
DSABLE
DSABLE
50
92
10
10
5
2
DSABLE
50
93
DEFAULT
VALUE
1
0
10
10
40
DSABLE
30
5
15