Carrier AquaEdge 19XRV series Operation, Maintenance And Installation Manual page 199

Single-stage or two-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

DESCRIPTION
Control Point
ECW Control Option
Temp Pulldown Deg/Min
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
RESET TYPE 2
Remote Temp
No Reset
Remote Temp
Full Reset
Degrees Reset
RESET TYPE 3
CHW Delta T
No Reset
CHW Delta T
Full Reset
Degrees Reset
Enable Reset Type
DESCRIPTION
Time Broadcast Enable
Daylight Savings
Start Month
Start Day of Week
Start Week
Start Time
Start Advance
Stop Month
Stop Day of Week
Stop Week
Stop Time
Stop Back
19XRV PIC III TEMP_CTL TABLE CONFIGURATION SHEET
RANGE
DSABLE/
0/1
ENABLE
2 to 10
ˆF (ˆC)
(1.1 to 5.6)
–30 to 30
ˆF (ˆC)
(–17 to 17)
–40 to 245
DEG F
(–40 to 118)
(DEG C)
–40 to 245
DEG F
(–40 to 118)
(DEG C)
–30 to 30
ˆF (ˆC)
(–17 to 17)
0 to 15 (0 to 8)
ˆF (ˆC)
0 to 15 (0 to 8)
ˆF (ˆC)
–30 to 30
ˆF (ˆC)
(–17 to 17)
0 to 3
BROADCAST (BRODEF) CONFIGURATION SHEET
RANGE
DSABLE/ENABLE
1 to 12
1 to 7
1 to 5
00:00 to 24:00
0 to 360
1 to 12
1 to 7
1 to 5
00:00 to 24:00
0 to 360
UNITS
POINT
ecw_opt
tmp_ramp
deg_20ma
res_rt1
res_rt2
deg_rt
restd_1
restd_2
deg_chw
res_sel
UNITS
HH:MM
MIN
MIN
CL-11
DEFAULT
VALUE
DSABLE
3
(1.7)
10
(6)
85
(29)
65
(18)
10
(6)
10
(6)
0
(0)
5
(3)
0
DEFAULT
VALUE
DSABLE
4
7
1
02:00
0
10
7
5
02:00
0