DAYLIGHT SAVING TIME CONFIGURATION — The
BRODEF table also defines Daylight Saving Time (DST)
changes. This feature is by default enabled, and the settings
should be reviewed and adjusted if desired. The following
line-item entries are configurable for both DST “Start” and
“Stop,” and they are defined in Table 8.
To disable the Daylight Savings Time function simply enter
0 minutes for “Start Advance” and “Stop Back.”
Table 8 — Daylight Saving Time Values
ITEM
DEFINITION
1 = January, 2 = February, …,
MONTH
12 = December.
DAY OF WEEK
1 = Monday,…, 7 = Sunday
1 = first occurrence of selected Day of
Week in the selected month, 2 = second
occurrence of the selected Day, etc. This
WEEK
is not necessarily what one would con-
clude from looking at a standard calendar.
For example, April 7, 2011, is Day 4 Week
1, but April 8, 2011, is Day 5 Week 2.
Time of day in 24-hour format when the
TIME
time advance or set back will occur.
“Advance” occurs first in the year, setting
the time ahead by the specified number of
ADVANCE/BACK
minutes on the selected date. “Back” sets
the time back by the specified amount
(later in the year).
START-UP/SHUTDOWN/
RECYCLE SEQUENCE (FIG. 32)
The timing of a normal start-up will
Local Start-Up —
change when Auto-Restart After Power Failure is enabled. See
the section on Auto-Restart After Power Failure. Local start-up
(or a manual start-up) is initiated by pressing the
LOCAL
menu softkey on the default ICVC screen. Local start-up can
proceed when the chiller schedule indicates that the CUR-
RENT TIME and CURRENT DATE have been established as
a run time and date, and after the internal timers have expired.
The timers include a 15-minute start-to-start timer and a 1-min-
ute stop-to-start timer, which together serve to prevent exces-
sive cycling and abuse of the motor. The value of these timers
is displayed as START INHIBIT TIMER and can be viewed on
the MAINSTAT and DEFAULT screens. Both timers must ex-
pire before the chiller will start. If the timers have not expired,
the RUN STATUS parameter on the MAINSTAT screen will
read TIMEOUT. If Auto-Restart After Power Failure is en-
abled, the start to start timer is now a maximum of 10 seconds,
and the stop to start timer is now a maximum of 10 seconds.
NOTE: The time schedule is said to be “occupied” if the
OCCUPIED ? parameter on the MAINSTAT screen is set to
YES. For more information on occupancy schedules, see the
sections on Time Schedule Operation (page 28), Occupancy
Schedule (page 47), and To Prevent Accidental Start-Up
(page 81), and Fig. 23.
If the OCCUPIED ? parameter on the MAINSTAT screen
is set to NO, the chiller can be forced to start as follows. From
the default ICVC screen, press the
and
MENU
STATUS
softkeys. Scroll to highlight MAINSTAT. Press the
SELECT
softkey. Scroll to highlight CHILLER START/STOP. Press the
softkey to override the schedule and start the chiller.
START
NOTE: The chiller will continue to run until this forced start is
released, regardless of the programmed schedule. To release
the forced start, highlight CHILLER START/STOP from the
MAINSTAT screen and press the
softkey. This
RELEASE
Page 61