Trouble Shooting Table - jablotron JA60K Installation Manual

Table of Contents

Advertisement

Of Line resistor 10k on the end of the loop, the control panel recognizes this situation and from this moment it will react to
any change of the resistivity (change of ±30% or more will trigger the input).
PGX
is an output (opened collector of a switching transistor to GND, max. 12V, 100mA). The function of this output is deter-
mined by the setting of parameter 23x in the programming mode (see 7.2.5). The control panel also wirelessly transmits
the PGX signal and unit UC-216 can be used as a remote output of this signal (see 8.1.3).
PGY
is an output (opened collector of a switching transistor to GND, max. 12V, 100mA). The function of this output is deter-
mined by the setting of parameter 24x in the programming mode (see 7.2.5). The control panel also wirelessly transmits
the PGY signal and unit UC-216 can be used as a remote output of this signal (see 8.1.3).
C
is a common contact of the alarm output relay, max. load 60V / 1A,. The relay is turned on during any alarm of the con-
trol panel.
NC
is a normally closed contact of the alarm output relay.
NO
is a normally open contact of the alarm output relay.
GND
is a common ground terminal of the power output (-).
SIR
is an external siren output. In normal mode there is a +U voltage. In the alarm mode there is a GND potential. Connect
an ordinary external siren to +U and SIR terminals (max. load 1A). A back up siren charging input should be connected
to the GND and the SIR terminals (during an alarm, the charging will halt).
+U
is a back up +13.8V power output. The permanent load should not be higher than 50mA. A short time consumption from
this output can be up to 1A (max. 10 minutes). This output is fused and supervised by the control panel. If it is over-
loaded, a control panel failure will be indicated (fault C).
fig.17

9. Trouble shooting table

Problem
alarm after first powering of
the control panel
impossible to enroll a de-
tector or a keypad
a fault is indicated on the
control panel and it is
beeping
telephone line failure is
indicated and the phone
Alarm system JA-60 "COMFORT"
possible cause
the control panel is not in factory default setting
location of the item (or the control panel) is not suit-
able and the radio signal level is too low (too far away
or an obstacle is in the way of communication)
check display for the reason of the trouble. Press key
N to disable beeping. The trouble information is
stored in the event memory and it can be reviewed
entering F4 anytime in the future
when you make a phone call longer than 15 minutes,
it is interpreted by the system that the tel. line is not
-
20 -
solution
perform a factory default reset, see
7.3
change location of the item, (fix it in
the new place temporary at first and
then try it)
check the reason of the trouble in
user instructions and fix it, or call
the installer
if you have this problem more often,
disable tel. line checking in pro-