SMC Networks HRS012-A Operation Manual page 47

Thermo chiller
Hide thumbs Also See for HRS012-A:
Table of Contents

Advertisement

Communication example
Your system
(Request):011700040003000B000204009B000134 [CR][LF]
(Response):011706000000000000E2 [CR][LF]
Request message
Code
01
Slave Address
17
Function
0004
Head address of specified register
0003
Quantity of register to read
000B
Head address of specified register
0002
Quantity of register to write
04
Quantity of byte to write
Information written to 000Bh (Circulating
009B
fluid set temperature)
0001
Information written to 000Ch (Stop flag)
34
LRC
HRS Series
○Slave Address: No 1
○Read three consecutive data from register 0004h, and write two
consecutive data from register 000Bh.
(Command to change the circulating fluid set temperature to <15.5
and read status and alarm information.)
Contents
Chapter 4
MODBUS communication function
Response message
Code
01
Slave Address
17
Function
06
Quantity of byte to read
0000
Information of 0004h (Status flag)
0000
Information of 0005h (Alarm flag 1)
0000
Information of 0006h (Alarm flag 2)
E2
LRC
HRX-OM-M091
o
C>,
This product
Data is sent and
received in ASCII
code.
Contents
4.8 Explanation of function codes
4-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents