Table 6: Gas Supply Requirements

3.5.3 Sound Pressure Levels

Sound pressure levels were measured at 4-
1/2' above the floor and 3' from the boiler at
the front, rear and two sides. See Table 7 for
decibel readings.

Table 7 Sound Pressure Levels

Model
Front
ARC1000
68
ARC1500
67
ARC2000
67
ARC2500
62
ARC3000
62

3.5.4 Pump and Piping Requirements

Pump piping and system piping must meet
the requirements of local codes and
jurisdictions. Good engineering practices
should be followed and considered for each
piping system used.
It is advised that the circulating pump for
each boiler be installed as close to the boiler
as possible in the line to the return connection
such that system water is pumped towards the
boiler.
Installing circulating pumps so that the water
is pumped away from the boiler is rarely
recommended.
Means to eliminate air from the boiler/piping
systems is a must. It is advised that an air
separator be installed as close as practical to
each boiler in the outlet pipe. Further, an air
vent should be installed at all high points
throughout the piping system.
24
Thermal Solutions, 1175 Manheim Pike, Lancaster, PA 17601 Web:
Phone: 717-239-7642 Fax: 877-501-5212 Email:
Decibel Levels
Tube
Right
Rear
Side
Side
61
63
64
60
61
63
60
61
63
62
66
61
62
66
61
It is recommended that a water meter be
installed in the make-up water system to the
boiler system. Scheduled recording of the
water meter register will show an indication of
a potential slow system leak in addition to
providing insight into any system problems.
Also, make-up water as well as water for the
initial system fill should be provided through
a water softener. Additionally, chemical
treatment of the system water is advisable.
Contact a qualified boiler water chemical
treatment company for their
recommendations. See section 3.8 for more
information.
See Appendix G for boiler water flow
pressure drop data and Appendix F for typical
boiler piping arrangements.
3.5.4.1 Water Flow Rates (Variable Primary
Pumping Systems)
Variable primary pumping systems shall be
capable of delivering no less than the
minimum and no more than the maximum
specified in Table 8 and Table 9 for each
boiler connected in the system.