3.3 Electrical Installation

3.3.1 Notice for wiring

Screwdriver torque:
A.
Connect cables with a screwdriver or other suitable tools and follow the torque listed below.
Horsepower
KW
0.25/0.5/1 0.2/0.4/0.75
0.25/0.5/1 0.2/0.4/0.75
2/3
1.5/2.2
1/2/3
0.75/1.5/2.2
B. Power cables:
Power cables are wires connected to L1(L), L2, L3 (N), T1, T2, T3, P and N. Choose cable in
accordance with the following criteria:
(1) Use cable with copper cores only. Select cable with insulation diameter based on working
conditions at 105
(2) For nominal voltage ratings, use cable rated at minimum 300V for 240Vac iDrives and
600V rated cable for 480Vac iDrives.
C. Control cables:
Control cables are connected to TM2 control terminals. Choose cable in accordance with the
following criteria:
(1) Use cable with copper cores only. Select cable with insulation diameter based on working
conditions at 105
(2) For nominal voltage ratings, use cable rated at minimum 300V for 240Vac iDrives and
600V rated cable for 480Vac iDrives.
(3) To avoid noise interference, do not run control cables in the same conduit or trunking as
power cables.
D. Nominal electrical specifications of terminal block TM1:
KW
0.2 / 0.4 / 0.75
0.2 / 0.4 / 0.75
1.5 / 2.2
0.75 / 1.5 / 2.2
Tightening torque
Power source
100-120V
200-240V
200-240V
380-480V
o
C.
P
P
o
C.
P
P
Horsepower
0.25 / 0.5 / 1
0.25 / 0.5 / 1
2 / 3
1 / 2 / 3
Chapter 3 Environment description and installation
Nominal torque for TM1 terminal
(lbs-ft / Nm)
1.286 / 1.74
(lbs-ft / Nm)
Power source
100-120V
200-240V
200-240V
380-480V
3-7
0.74 / 1.00
Volts
Amps
600
15
600
40