1.1.2 During Power up

The inverter still has control power if the time of power loss is very short. When the
power is re-supplied, the inverter operation is controlled by parameter b31.
The inverter operation is controlled by A00 and b33 and the status of (FWD/REV RUN
switch) when power is re-applied (and b31 /b32) Power loss ride through / Auto reset
after fault.
1. When A00=000, the inverter will not auto restart when power is re-applied.
2. When A00=001 and operation switches (FWD/REV RUN) are OFF, the inverter will
not auto restart when power is re-applied.
3. When A00=001 and operation switch ON and b33=000, the inverter will auto restart
when power is re-applied. Please turn OFF the run (start) switch to avoid damage to
machine and injury to operator before the power is re-applied.
When b33=000 (direct start on power up), please refer to the description of b33 to verify
the safety of operator and machine.

1.1.3 Before operation

Make sure the model and capacity are the same as those set by b89.
1.1.4 Earth / ground leakage current
Warning ! iDrive EDX series built-in filter type can give leakage current > 3.5mA.
ALWAYS ENSURE INVERTER IS CORRECTLY EARTHED / GROUNDED..
Operation with ungrounded supplies:
DO NOT use iDrive EDX inverters on ungrounded (floating) power supplies.
Operating
iDrive EDX
1. Inverter leakage current may cause nuisance trip when RCD setting is <100mA
2. Only one inverter should be supplied from each RCD.
Danger
Caution
Warning
with Residual Current Device (RCD):
1-2
Chapter 1
Safety Precautions