5.4 Routine periodic checks
To ensure stable and safe operation, check and maintain the inverter regularly.
The table below lists the items requiring checking to ensure safe operation.
Check these items 5 minutes after the "Charge" indicator goes out to prevent service persons from
being hurt by residual electric power.
Items
Confirm the temperature
and humidity around the
machine
Circumstances
around the
machine
Are there inflammable
materials in proximity?
Any unusual vibration from
the machine
Installation and
grounding of
Is the grounding resistance
the inverter
/ earth-loop impedance
correct?
Input power
Is the voltage of the main
voltage
circuit correct?
External
Are secure parts loose?
terminals and
Is the terminal base
internal
damaged?
mounting
screws of the
Obvious corrosion?
inverter
Trapped or over-heated?
Internal wiring
of the inverter Any damage of to the
insulation?
Heat sink
Build-up of dust deposits
Build-up of conductive
metal or oil sludge
Printed circuit
board
Discolored, overheated, or
burned parts
Check if operating ok or
unusual vibration and noise
Cooling fan
Build-up of dust deposits
Build-up of dust deposits
Power
Check
circuit
component
terminals
Any unusual odor or
leakage of electrolyte
DC Link
Any splits / swelling to case
Capacitor(s)
or end caps?
High temperatures?
Checking
Details
period
Week Year
between
Chapter 5 Trouble shooting and maintenance
Methods
Measure with
thermometer and
hygrometer
according to
installation notices.
Visual check
Visual, hearing
Measure the
resistance
Measure the
voltage with a
multi-meter
Visual check
Check with a
screwdriver
(Make sure power
is OFF first)
Visual check
Visual check
Visual check
Visual or hearing
check
Visual check
Visual check
Measure with a
multi-tester (diode
checker)
Visual check
5-13
Criteria
Temperature: -10 –
o
50
C
Humidity: Below 95%
RH
No foreign matters
No foreign matters
Secure screws
According to national
Improve the
regulations
grounding path
Voltage must conform
Improve power
with the specifications
supply
No abnormalities or
Secure or send back
cross-threading
for repair
No abnormalities
Inform your supplier
No abnormalities
Clean away dust
Clean up or replace
No abnormalities
the circuit board
Replace the cooling
Clean, quiet,
fan
operating OK
Clean
No abnormalities
Clean up
No short circuit or
Replace power
damage
to
input
component or
/output circuits
inverter
Replace capacitor or
inverter
No abnormalities
Remedies