3 TRANSPORT – STORAGE – UNPACKING

3.1 VISUAL INSPECTION

Upon receiving the goods, make sure that they corresponds to the material indicated in the delivery note.
Carefully examine the packed unit(s) for any sign of physical damage. Two TiltWatch indicators (see Figure 3) are
placed on two sides of the packed unit, in a well visible position. They should both be intact and not red color. If
tipping has occurred the white arrow becomes red, like shown on the Figure 3 below.
In case of damaged unit(s) or even only suspect of damaged (TiltWatch is red) inform immediately:
The carrier
The manufacturer
VISIBLE TRANSPORT DAMAGES MUST BE CLAIMED TO THE CARRIER IMMEDIATELY
AFTER RECEIPT.
IMPORTANT
OTHER CLAIM FOR SHIPPING DAMAGE MUST BE FILED ALSO IMMEDIATELY AND THE
NOTES
CARRIER MUST BE INFORMED WITHIN 7 DAYS OF RECEIPT OF THE EQUIPMENT. THE
PACKING MATERIALS SHOULD BE STORED FOR FURTHER INVESTIGATION.
Figure 3: TiltWatch indicator: left when intact and right when tipping has occurred.

3.2 STORAGE

The packing of the goods protects it from mechanical and environmental damage. UPS and Battery cabinets
should be store in its original packaging. Make sure that the goods are stored indoor, protected from water and
sunshine in a clean environment.
THE RECOMMENDED TEMPERATURE FOR STORAGE OF THE UPS SYSTEM AND
BATTERIES IS BETWEEN +20 °C AND +25°C, HUMIDITY < 95% (NON-CONDENSING).
IMPORTANT
FOR UPS SYSTEM ONLY THE STOREAGE TEMPERATURE CAN BE BETWEEN -25 °C
NOTES
AND +70°C, HUMIDITY < 95% (NON-CONDENSING).
BEFORE SWITCHING ON THE UNIT(S), MAKE SURE THE AMBIENT TEMPERATURE HAS
REACHED THE OPERATION TEMPERATURE RANGE WHICH IS 0°C - +40°C.
SEALED BATTERIES MUST NEVER BE STORED IN A DISCHARGED OR PARTIALLY
DISCHARGED STATE.
EXTREME TEMPERATURE, UNDER- AND OVERCHARGE AND OVERDISCHARGE WILL
DESTROY BATTERIES!
If the UPS is delivered without batteries, the manufacturer is not responsible for any damage or malfunctioning
caused to the UPS by incorrect wiring. For long-term storage make sure that the battery is fully recharged every 6
months. Before and after storing, charge the battery.
04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx
Modifications reserved
Page 12/78 ABB