Chapter 4
Using the HIM
Initiating PowerFlex 750-
Series Drive Port Verification
60
The information in this section does not apply to PowerFlex 7-
IMPORTANT
Class drives.
Upon powerup, the HIM verifies that the PowerFlex 750-Series drive has
initiated Port Verification. The host drive then checks for port conflicts. If any
conflicts are present, a Device Conflicts pop-up box appears listing all devices
with conflicts.

Conflict Types

If the conflict can be resolved, a '!' symbol precedes the port number. If the
conflict cannot be resolved without removing or replacing the device, an 'X'
symbol precedes the port number. There are five possible conflict types.
Symbol
Conflict Type
!
Changed
!
Requires Configuration
X
Not Functioning
X
Not Supported
X
Invalid Duplicate
In the Device Conflicts pop-up box, scroll up or down to highlight/select an
individual device row and press the INFO soft key. Another pop-up box appears
for the selected device showing the type of conflict and related information.
If information is available for the device that previously occupied that port, it will
also be shown.
Use the FIX soft key—displayed only if all conflict types are 'Changed' or
'Requires Configuration'—to resolve conflicts. After pressing the FIX soft key, a
pop-up box will appear asking to confirm that the new device(s) should be
accepted. Press the ENTER soft key to affirm and resolve the conflicts for all
devices. Thereafter, the HIM will re-read the drive Port Verification information
to ensure that no further conflicts exist.
Please note the following important conflict resolution information:
IMPORTANT
• The Device Conflict pop-up window remains on the screen until all conflicts
• All conflicts must be resolved to access a Folder screen or Control screen.
• The host drive will not be able to run while any conflicts are present.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
are resolved.
Only the
(Stop) key and the assigned soft keys (INFO and FIX) will be
functional until no conflicts exist.