Setting Display Flashing For Fault Indication - Allen-Bradley PowerFlex 20-HIM-A6 User Manual

Human interface module
Hide thumbs Also See for PowerFlex 20-HIM-A6:
Table of Contents

Advertisement

Chapter 4
Using the HIM
Setting Display Flashing for
Fault Indication
40
Whenever a fault for the host drive or any of its connected peripherals is
detected, a pop-up Fault Display screen (see
the Status Bar flashes to alert the operator. However, you can change the flash
mode for the Fault Display screen to one of the following modes:
• Flash Bklite; selects the entire LCD screen to flash.
• Flash Status (default); selects only the Status Bar (item 1,
• Flash None; selects no flashing for the Fault Display screen.
Follow these steps to change the flash mode for the Fault Display screen.
1. Access HIM Parameter 04 - [Fault Dspy Type] using either the Direct
Parameter Access method
(page
43).
2. Press the EDIT soft key to display the Edit Fault Dspy Type pop-up box.
6WRSSHG
 +]
(GLW )DXOW 'VS\ 7\SH
Flash Bklite
  
(6&
3. Use the
and
erroneous entry, use the
4. Press the ENTER soft key to enter your selection and return to the
parameter screen.
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
(page
42) or Alternate Linear List method
$872
)
0
(17(5
soft keys to select the desired flash mode. To delete an
soft key.
page
30) appears. By default, only
Figure
3) to flash.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 20-him-c6s

Table of Contents