Checking Drive And Peripheral Firmware Revisions - Allen-Bradley PowerFlex 20-HIM-A6 User Manual

Human interface module
Hide thumbs Also See for PowerFlex 20-HIM-A6:
Table of Contents

Advertisement

Checking Drive and
Peripheral Firmware
Revisions
Table 2 - 20-HIM-A6 and 20-HIM-C6S HIM Events
Code
Event
1
Reserved
2
Device Power Up
3
Device Reset
4
EEPROM CRC Error
5
App Updated
6
Boot Updated
7
Watchdog Timeout
8
DPI Bus Off
9
DPI Ping Timeout
10
DPI Port Invalid
11
DPI Port Changed
12
DPI Host Reset
13
DPI Baud 125K
14
DPI Baud 500K
15
DPI Host Invalid
16
DPI Dup Port
17
DPI Type 0 Logon
18
DPI Type 0 Time
19-23
Reserved
24
DPI Msg Timeout
25
DPI Manual Reset
Follow these steps to check the firmware revision of the drive or its peripherals.
1. Access the Status screen (see
2. Use the
version you want to view (for example, Port 00 for the host drive).
3. Press the
4. Use the
5. Use the
6. Press the
6WRSSHG
 +]
3RZHU)OH[ 
3URGXFW 6HULHV $
3URGXFW 5HYLVLRQ 
3URGXFW 6HU 1XP 
²0DLQ &RQWURO %RDUG
): 5HYLVLRQ 
(6&
723
Rockwell Automation Publication 20HIM-UM001D-EN-P - February 2013
Description
A normal power up.
The HIM was reset due to a manual reset command or program crash.
The HIM EEPROM Data Storage Device is corrupt.
The HIM application firmware has been updated.
The HIM boot firmware has been updated.
A program crash has occurred.
A DPI Bus Off fault was detected.
A DPI Ping Timeout fault was detected.
A DPI Port ID fault was detected.
A DPI Port Changed fault was detected.
The host has sent a reset message.
The DPI data rate is detected at 125K bits/second.
The DPI data rate is detected at 500K bits/second.
The HIM will not connect to this type of host.
Another DPI device is already connected to this port.
The DPI log on was completed successfully.
A DPI Type 0 Command has timed out.
A message to a DPI device has timed out.
A reset command was sent through a fault object.
Figure
6).
or
key to scroll to the Port of the device whose firmware
key to display its last-viewed folder.
or
key to scroll to the DIAGNOSTIC folder.
or
key to select Device Version.
(Enter) key to display device version information.
$872
)
(1'
3*83 3*'1
Using the HIM
Chapter 4
47

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerflex 20-him-c6s

Table of Contents