Operation; Remote Management; Local Management - CyberPower PDU81001 User Manual

Hide thumbs Also See for PDU81001:
Table of Contents

Advertisement

Operation

Remote Management

The remote management function provides monitoring of the MBO PDU
operational information, controlling outlets and utilizing SNMP functionality.
Web
Remote management can be performed via web interface. To access the web interface,
please follow the instructions below:
1. Enter the IP address of the PDU into a web browser (Internet Explorer, Firefox).
2. Enter the user name and password of the PDU device at the authentication screen.
Note: The default username is "admin/cyber" and the default password is "admin/
cyber".
Telnet and SSH
The CyberPower PDU provides Telnet and Secure Shell (SSH) as Remote Management
methods. Telnet uses user name and password as basic security while SSH has a
higher security level with encryption of the transmitted packets including user name,
password, and data. Configure the Setting of Telnet and SSH on the Web Interface. The
default user name and password is admin/cyber; admin/cyber.
SNMP
The CyberPower PDU supports SNMPv1 and SNMPv3 Remote Management
protocols. Download the CyberPower MIB file and add it to an SNMP-supporting
management software. Default read/write community is public/private for
SNMPv1. SNMPv3 provides a higher security level than SNMPv1 by encrypting
the transmitted packet. Configure the settings of the SNMPv1/SNMPv3 on Web
Interface.

Local Management

LCD Operation
The LCD display provides instant information, such as voltage, current and
power, for the PDU. In addition, users can use the interface to configure each
PDU parameters and control each outlet on the Switched PDU. The LCD detects
the installation orientation of the PDU (horizontally or vertically), therefore
automatically rotates the screen to best fit the reading direction.
A. Scroll Mode: The PDU information will display in following order automatically
when "Scroll Mode On" is configured.
Device Information
Bank 1 Information (2U series)
Bank 2 Information (2U series)
Environment Status (Displays when the ENVIROSENSOR is connected)
Alert
B. Main Menu Map
Current
Alert
Log
Device
Meter
Bank
Outlet
Device
Control
Bank 1/2
Outlet 1-N
LCD
Setting
Reset
Reboot
Model Name
Serial Number
About
Network
Hardware Version
Firmware Version
©2016 Cyber Power Systems, Inc. All rights reserved.
Immediate On
Delay On
Immediate Off
Delay Off
Reboot
Delay Reboot
Color
Brightness
Direction
Screen off
Account (User Name and Password)
Except TCP
To Default
13