Product Features (2U Models)
Front Panel Description
NEMA Type
M
IEC Type
M
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility power or UPS.
B. AC Output Receptacles - Provides power for connected equipment.
C. Status Indicator - Indicates the condition of the PDU (eg. load or
environment status).
D. Circuit Breaker – Provides overload protection.
E. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port) – Used for
ENVIROSENSOR or chaining to previous PDU (future use).
F. USB Port - Used to upgrade the firmware via a flash drive.
G. Serial Port (RJ45 modular port) - Used to connect to a PC and control
the PDU locally via SSH/Telnet.
H. Daisy Chain (Out) Port – Used for chaining to next PDU (future use).
I. Ethernet Port – Used to connect PDU to the network.
J. Multifunction LCD Readout - Displays various PDU information such as
power and load condition.
K. Select Button - Used to control the LCD screen and toggle through the
available information options.
L. Enter Button - Used to choose selected items, enter to next level menu
or return to previous menu.
M. Outlet Indicator (switched series only) – Indicates if the outlet is
providing power to connected equipment.
Rear Panel Description
A. Ground Stud - Use to ground the PDU.

Technical Specifications

PDU81003
PDU71003
Model Name
PDU41003
PDU31003
Input
Nominal Voltage
100-120V
Frequency
Maximum Input Current
Plug Type
NEMA L5-30P
Power Cord Type
Power Cord Length
Output
Nominal Voltage
100-120V
Maximum Output Current
Maximum Output Current
Band Number
Outlet Type
NEMA 5-20R
Outlet Number
Circuit Breaker
Management and Communications
Multifunction LCD Readout
Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
Networking
Serial Port
Sensor Capable
Physical
Dimensions (H x W x D)
Environmental
Humidity
Altitude
Temperature
Safety Approvals
Certifications
* All specifications are subject to change without notice.
6
©2016 Cyber Power Systems, Inc. All rights reserved.
PDU81007
PDU81008
PDU81009
PDU71007
PDU71008
PDU71009
PDU41007
PDU41008
PDU41009
PDU31007
PDU31008
PDU31009
200-240V
50/60Hz
24A UL (Derated)
NEMA L6-30P
SR (10 AWG)
12 ft/3.65 m
200-240V
24A UL (Derated)
20A (per bank)
2
IEC C13
12 IEC C13/ 4 IEC C19
IEC C19
16
10
Yes
PowerPanel® Business Edition
Yes
RJ45 (Modular)
Optional
3.5" x 17.05" x 4.41"/ 88mm x 433mm x 112mm
0 to 95% Non-condensing
11480 ft/3500 m
o
o
o
o
32
F to 113
F /0
C to 45
C
UL 60950-1, FCC Class A

Advertisement

Table of Contents
loading