What to do if you want to change the IP Address at the Control Station

For a new Control Station that does not have a valid database, proceed with step 1 in the table below. If the
Control Station has a valid database and you want to change the existing IP address, the database memory
must first be cleared by performing the cold start procedure listed above. Once the database has been
cleared, the following procedure may be used to enter a new IP Address at the Control Station.

Changing or entering IP Address

Step
1
Disconnect power from the unit.
2
Press and hold the F1 and the fourth Soft Key (Logoff for 900CS10 and F4 for 900CS15)
simultaneously and hold them down while applying power.
3
Keep the keys pressed until a pop-up keypad appears. Enter an IP Address that has the same
subnet as your PC and the HC900 Controller and a unique fourth number. Press the green
arrow to enter the IP Address.
4
The following message will appear with the newly entered IP Address:
" INVALID DATABASE
IP Address is 192.168.1.nnn with TCP/IP download enabled on port 789.
MAC Address is...
Hold 1st and 4th keys on power-up to configure IP"
5
Using the new IP Address, download a Station Designer database file to the 900 Control
Station by means of the Link menu.
174
Action
900 Control Station User Guide
Revision 9
May 2014

Hide quick links: