View/Edit Profile Segments

This display lets you edit the profile segments (setpoints and events) of the working program. Edits do not
affect profiles in memory unless you save them.
ATTENTION
Program must be in READY, HOLD, or STOP state before segments can be edited.
TIP
• Edits are allowed to any segment of the program, including the current segment.
• If edit is to current segment and segment is a ramp:
- If the ramp type is edited, then the time remaining is recalculated and the ramp
rate is adjusted accordingly.
- If the ramp rate is edited, then the time remaining is adjusted accordingly.
- Changes to the ramp starting setpoint will be ignored for the current execution of
the segment, but will be used for subsequent execution if the segment is included
in a loop.
• If edit is to current segment and segment is a soak:
- Changes to the soak setpoint will result in a step change.
- Changes to the time will cause recalculation of the segment time remaining. If
the result is less than or equal to 0, the program will advance to the next segment
upon returning to RUN state.
• If the current segment is a ramp and the starting value of the following segment is
changed, then the time remaining in the ramp segment will be adjusted accordingly
but the ramp rate will remain unchanged.
• Edits to soak setpoints will result in a step change at the next segment unless the
starting value of that segment is changed to the same value as well.

Edit Type and Value

Press the Edit Type and Value button to display the setpoint parameters below.
Item
Profile number
Profile Name
Profile Description
Segment #
Segment Type
Starting Value
Time/Rate
Revision 9
May 2014
Memory location of the profile that is being run by the Setpoint
Programmer.
Name of the selected profile.
Description of the profile.
Segment being edited.
Ramp or Soak. Last segment must be a soak.
Starting value of the segment.
Range = 0.00 hr. to 999.99 hr. or 0.00 min. to 999.99 min. The function of
this value depends on the Ramp Type.
900 Control Station User Guide
Setpoint Programmers
View/Edit Profile Segments
Description
131