Honeywell 900 User Manual page 30

Control station
Table of Contents

Advertisement

Main Menu
Controller
Item
Controller Mode
Frequency (Hz)
Cycle Time (Sec)
CPU Percent used
Peak time (sec)
Control Block
Overruns
Fast Logic Cycle Time
(Sec)
Fast Logic CPU Per
Cent Used
Fast Logic Peak Time
(Sec)
Fast Logic CB
Overruns
18
Controller's mode of operation:
RUN: Controller is running normally.
Note: (For C30S, C50S, C70S and C75S Controllers only)
Blinking RUN text on master slide on lower right hand corner indicates
controller is in invalid mode, which means there are some forced output(s)
present in Safety portion of the controller configuration and user changed the
controller mode to RUN-LOCKED mode from RUN-PRGM mode.
PROG: Controller is in Program mode.
OFLN: Controller is in Offline mode.
FAULT: A fault was found reading the Controller switch.
NO COMM: This is displayed if controller is not responding.
Line frequency. Used for configuring the conversion time of the A/D converter.
The analog control cycle time in seconds. This value is determined from the
execution time estimated from the configured control scheme. Cycle Time and
Fast Cycle Time increase (slow down) as the following increase: CPU % Used,
Fast CPU % Used, Dynamic Memory, Config Memory. Also, extensive use of
Free Form Logic blocks (as opposed to equivalent gate logic) can substantially
increase Fast Cycle Time.
Calculation of percentage of time the CPU is active during the analog cycle time
Maximum time used to complete the analog cycle
Number of times that the processing of the analog control blocks exceeds the
allocated analog cycle time
Cycle Time and Fast Cycle Time increase (slow down) as the following
increase: CPU % Used, Fast CPU % Used, Dynamic Memory, Config Memory.
Also, extensive use of Free Form Logic blocks (as opposed to equivalent gate
logic) can substantially increase Fast Cycle Time.
Calculation of percentage of time the CPU is active during the processing of
digital control blocks
Maximum time used to complete the digital control cycle
Number of times that the processing of the digital control blocks exceeds the
allocated digital cycle time