Honeywell 900 User Manual page 138

Control station
Table of Contents

Advertisement

Setpoint Programmers
Setpoint programmer Operate
Item
Title
SP Profile Information
Profile Number
Profile Name
Profile Description
Total Elapsed Time
State
Segment Information
Segment number
Elapsed Time
Time Remaining
Segment Type
Operation Buttons
Run
Hold
Advance
126
Name of the selected setpoint programmer block.
Memory location of the profile that is being run by the Setpoint
Programmer.
Name of the selected profile.
Description of the selected profile.
Total time the profile has been in Run, Hold and GHold states.
READY: Profile is at the beginning of segment and is ready to run. All
events are OFF.
HOLD: Profile is paused at the setpoint value shown.
RUN: Profile is executing normally.
GHOLD: Profile is paused because of excessive deviation.
STOP: Profile has reached the end of the last segment.
DISABLE: Profile is prevented from starting until the programmer disable
control is ON.
Current segment
Time elapsed in the segment. Run time only.
Time remaining in the segment.
Text shows type of current segment: ramp or soak.
The current and next segment types are shown graphically. In the above
example, the current segment is ramping up, the next segment is a soak.
Start a program that is in HOLD or READY state.
Put program in HOLD.
Jump to the next segment.
When the program is already in the last segment, the advance request is
ignored.
Programs cannot be advanced to the first segment. Current state must
either READY or HOLD.