Table 11 Ethernet Port E1/E2: Port Diagnostic Status - Honeywell 900 User Manual

Control station
Table of Contents

Advertisement

Main Menu
Communications
Status
GOOD
N/A
SETUP ERROR
Controller/network
names determined on
network are illegal
NO IP ADDRESS
IP address is not
configured
HARDWARE
Ethernet port tests
FAILURE
failed during power-up.
DHCP Failure
DHCP is configured,
and no IP address has
been granted.
28

Table 11 Ethernet Port E1/E2: Port Diagnostic status

Possible Cause
N/A
Rack 1 monitor block's
COMPORT DIAG is set to
FAILED.
Rack 1 monitor block's
RACK OK pin is turned off.
ASYS (SYSTEM
MONITOR) block's HW OK
pin is turned off.
Same as above
Same as above
Same as above
900 Control Station User Guide
Controller Action
N/A
Correct the setup problem.
If a DHCP server is present,
download a configuration that
uses DHCP.
Enter an IP address.
Replace CPU module.
Check the DHCP server.
Download a configuration with
DHCP required.
Ethernet Port E1/E2 Status
What to do
Revision 9
May 2014