Callback Acknowledgment; Call Cancel; Auto Test; Unit Reset - Phonetics SENSAPHONE EXPRESS II User Manual

Remote monitoring system
Table of Contents

Advertisement

When Call Cancel is enabled, Express II will stop dialing out
when the alarm clears, even if the alarm has not yet been
acknowledged. When Call Cancel is disabled, Express II
will continue dialing out for the alarm until it receives ac-
knowledgment, even if the alarm clears in the meantime.
7. Auto Test - This feature allows you to simulate an alarm
on an input to test the dial out procedure. When you call
Auto Test, it will ask you to specify an input number to test.
NOTE: Auto test will make actual phone calls to the Phone
Contacts using the specifications you programmed. You
must acknowledge the alarm as if it were real.
Also, the Auto Test feature will not work if "Call Cancel" is
enabled (see #6 above).
8. Unit reset- Generally for factory use, the Unit Reset
feature will reset the various unit parameters you've pro-
grammed in. Should you want to reset the unit, enter a
reset code of "159," and press Enter. Choose from Full
Reset, Programming Reset, or Voice Reset.
Note: only "Voice reset" offers options. Selecting the other
two will clear system parameters.
9. Unit configuration- The Unit Configuration menu offers
you three choices:
1 - RS232 Rate (default: 9600 baud): This is the
baud rate for the RS232 port to which you would
connect a printer. Its default setting is 9600 baud.
You can reset it in a range from 1200 to 38,400.
2 - Callback Rings (default: 10): As mentioned
under the "Callback Acknowledgment" section
above, the Express II will not answer your call to
acknowledge an alarm until the phone has rung
ten times. This is the default setting. If you wish,
you can change that number here.
3 - Ack over voice (default: disabled): This
feature, when activated, allows you to punch in a
code number of "555" while the unit is speaking to
cut off the message. This is a factory testing
feature and in practice is not a dependable
override. Generally it should be left disabled.
(See Chapter 5: System, Acknowledgement Code
for more information on setting the code number.)
®
44
Sensaphone
Express II User's Manual

5. Callback acknowledgment:

1) Press 5 for Callback Acknowledge.
2) Enter 1 to enable.
Enter 0 to disable.

6. Call Cancel:

1) Press 6 for Call Cancel enabling.

7. Auto Test:

1) Press 7 for Auto Test.
2) Enter input number.
3) Press Enter.
Note that Call Cancel and Auto Test
are mutually exclusive.

8. Unit Reset:

1) Press 8 for Unit Reset
2) Full reset: "Enter" clears everything.
Programming reset: clears program-
ming settings you've entered and
returns them to the defaults.
Voice messages reset: resets
individual expansion card messages
and/or the voice ID message.

9. Unit Configure

1) Press 9 for Unit configuration.
Choose from:
RS232 rate: Set this rate from 300-
38,400 bauds
Callback rings to answer: choose a
new number if you don't want 10.
Ack over voice: choose from
disabled/enabled.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents