Problem
IV. OTHER
1. Alarm status of input
is incorrect.
2. The unit won't
perform an autotest.
3. The unit calls again
with the same alarm
after I acknowledge it.
®
74
Sensaphone
Express II User's Manual
Cause
Incorrect input normality.
The call-cancel feature is
enabled. An auto test won't
execute if this feature is
enabled.
Alarm reset time is set at too
short an interval.
Alarm condition is sporadic,
going on and off.
Solution
Reprogram the input type to the
correct normality. See "Inputs" in
Chapter Five.
Disable the Call Cancel feature. (See
Chapter Five)
Increase the "Alarm reset" value. See
"Alarm Reset Time" sections in
Chapter Five and "Alarm is
Acknowledged" in Chapter Six.
Lengthen recognition time. See
various "Recognition Time" sections in
Chapter Five.