DATA LOG [9]

Express II has two logging features, the Input Log and the
Activity Log. The Data Log features require the use of a
printer with a serial port. If either data log is enabled,
Express II will send information to the serial port to be
printed via the RS232 socket located to the right of the
phone jack and above the orange terminal block at the
bottom of the unit.
1. Input/Output Log - Logs the input (or output) values on a
user-defined basis. The menu offers four choices:
1. Enable/Disable: 1=disable; 2=enable
2. Time between logs: set the hours, minutes, and
seconds. The minimum allowed time is 5 seconds; the
maximum is 12 hours, 59 minutes, 59 seconds.
3. Number of inputs: the maximum this can be set
to is 40.
4. Line length: this determines the number of
characters that a data log printout will allow on each line.
The default setting is 80 characters per line. Check your
printer setup before changing this number.
2. Activity Log - Logs all system and alarm activity. This
includes programming changes, alarms occurring and
clearing, acknowledgments, any call-ins to the unit and
alarm dial outs.
NOTE:
Once datalogging is enabled, the system will automatically
default to an RS232 rate of 9600 baud. If your target printer
is not configured to 9600 baud, refer to your printer manual
to adjust the printer's baud rate. (See also "Unit configura-
tion" in the following section.)
®
42
Sensaphone
Express II User's Manual
DATA LOG PARAMETERS

1-Input/Output Log:

1) Press Program.
PROGRAM
2) Press Data Log.
WXY
9
DATA LOG
Data Log menu will appear on local
display.
> 1- Input Data Logs
2- Activity Logs
3) Press 1 for Input/Output Log.
4) Press 1 for Enable/Disable.
Press 1 to Disable; 2 to Enable
5) Press 2 Time Between Log.
Enter hours, minutes, seconds.
6) Press 3 for Number of Inputs.
Enter the number of inputs to be
monitored.
7) Press 4 for Line length.
Enter number of characters you want
per line in your printout.

2-Activity Log:

1) Return to the Data Log menu.
Press 2 for Activity Log.
2) Press 1 to disable.
Press 2 to enable.