POWER [7]

Express II monitors AC power failure and low
battery condition. Power monitoring and low battery
monitoring is explained below.

1= AC Power

2= Battery
Power Failure
1. Power Failure Monitoring enable/disable - This
command enables or disables the power failure
detection. When enabled, Express II will monitor
power and dial out if a valid failure occurs. When
disabled, Express II will not dial out for a power
failure. 1 = disable, 2 = enable. The default is
enabled.
2. Power Recognition Time - The power recogni-
tion time is the length of time that a power failure
must exist continuously before Express II will
recognize it as an actual alarm and initiate the dial
out sequence. Power recognition time may be
programmed from 0 seconds to 12 hours. The
default is 5 minutes.
3. Alarm Reset Time - After power failure is ac-
knowledged, Express II stops the dial out sequence.
However, the power failure condition will still exist
until power is restored. If the power is not restored
after a certain amount of time, Express II can be
programmed to restart the dial out sequence. This
is called the alarm reset time. This parameter may
be programmed from 0 seconds to 12 hours.
If the alarm reset time is programmed to 0 seconds,
the feature is disabled. Express II will not restart
the dial out regardless of how long the alarm exists.
4. Dial Out Selection - You may program Express
II to call a specific set of Phone Contacts for power
failure only. This is called the Dial out selection. To
return to the default setting, all contacts, press '9'
'9', and then press ENTER.
®
38
Sensaphone
Express II User's Manual

POWER PARAMETERS

AC POWER
1) Press Program.
PROGRAM
2) Press Power.
PRS
7
POWER
3) Power menu will appear. Press 1 for AC
Power Parameters.
The AC Power menu will then be
displayed.
> 1- Failure monitor
2- Recognition time

3- Alarm reset time

4- Dialout Selectn
1-Power Failure Monitoring:
1) At the AC Power menu press 1 for
Failure Monitor.
2) Press 1 to disable.
Press 2 to enable.

2-Power Recognition Time:

1) Press 2 at the AC Power menu.
2) Enter hours.
Enter minutes.
Enter seconds.
3-Alarm Reset Time:
1) Return to the AC Power menu. Press 3
for Alarm Reset time.
2) Enter hours.
Enter minutes.
Enter seconds.

4-Dialout Selection:

1) Press 4 at the AC Power menu for Dial
Out Selection.