Maximum Number Of Calls; Call Delay Time; Intercall Delay Time - Phonetics SENSAPHONE EXPRESS II User Manual

Remote monitoring system
Table of Contents

Advertisement

6. Intercall Delay Time - If an alarm call has not been
acknowledged, the intercall delay time is the length of time
between each phone call that Express II will wait before
dialing the next phone number. This parameter may be
programmed from 0 to 12 hours. The default is 30 seconds.
2) Then, enter number of times the
message will repeat itself for each
call during an alarm.
4-Maximum Number of
Calls:
Return to Dial-Out menu.
1) Press 4 for MAXIMUM # OF CALLS.
2) Enter the total number of outgoing
calls alloted for an alarm.(prior to
acknowledgement)

5-Call Delay Time:

Return to Dial-Out menu.
1) Press 5 for CALL DELAY TIME.
2) Enter Hours.
3) Enter Minutes.
4) Enter Seconds.

6-Intercall Delay Time:

Return to Dial-Out menu.
1) Press 6 for INTERCALL DELAY
TIME.
2) Enter Hours.
3) Enter Minutes.
4) Enter Seconds.