YASKAWA U1000 Quick Start Manual page 97

Industrial matrix drive
Hide thumbs Also See for U1000:
Table of Contents

Advertisement

No.
Name
Communication Fault
H5-05
Detection Selection
Drive Transmit Wait
H5-06
Time
H5-07
RTS Control Selection
Communication Fault
H5-09
Detection Time
Unit Selection for
H5-10
MEMOBUS/Modbus
Register 0025H
Communications
H5-11
ENTER Function
Selection
Run Command
H5-12
Method Selection
Pulse Train Input
H6-01
Terminal RP Function
Selection
Pulse Train Input
H6-02
Scaling
H6-03
Pulse Train Input Gain
H6-04
Pulse Train Input Bias
Pulse Train Input Filter
H6-05
Time
Pulse Train Monitor
H6-06
Selection
Pulse Train Monitor
H6-07
Scaling
Pulse Train Input
H6-08
Minimum Frequency
Motor Overload
L1-01
Protection Selection
Motor Overload
L1-02
Protection Time
<1> Available in drive software versions PRG: 1015 and later.
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide
Description
0: Disabled
1: Enabled. If communication is lost for
more than two seconds, a CE fault will
occur.
Set the wait time between receiving and
sending data.
Note:
Cycle power for the setting
to take effect.
0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when
sending.
Note:
Cycle power for the setting
to take effect.
Sets the time required to detect a
communications error.
0: 0.1 V units
1: 1 V units
0: Drive requires an Enter command
before accepting any changes to
parameter settings.
1: Parameter changes are activated
immediately without the Enter command.
0: FWD/Stop, REV/Stop
1: Run/Stop, FWD/REV
0: Frequency reference
1: PID feedback value
2: PID setpoint value
3: V/f Control with Simple PG feedback
(possible only when using motor 1 in V/f
Control)
Sets the terminal RP input signal frequency
that is equal to 100% of the value selected
in H6-01.
Sets the level of the value selected in H6-01
when a frequency with the value set in
H6-02 is input.
Sets the level of the value selected in H6-01
when 0 Hz is input.
Sets the pulse train input filter time
constant.
Select the pulse train monitor output
function (value of the o-oo part of
Uo-oo).
For example, enter "501" for U5-01.
Sets the terminal MP output signal
frequency when the monitor value is 100%.
For example, to have the pulse train monitor
output equal the output frequency, set
H6-06 to 102 and H6-07 to 0.
Sets the minimum frequency for the pulse
train input to be detected. Enabled when
H6-01 = 0, 1, or 2.
0: Disabled
1: General purpose motor (standard fan
cooled)
2: Drive dedicated motor with a speed range
of 1:10
3: Vector motor with a speed range of 1:100
4: PM motor with variable torque
5: PM motor with constant torque control
6: General purpose motor (50 Hz)
Default setting is determined by parameter
A1-02, Control Method Selection.
Sets the motor thermal overload protection
(oL1) time.
No.
Name
Momentary Power
L2-01
Loss Operation
Selection
Stall Prevention
L3-04
Selection during
Deceleration
Number of Auto
L5-01
Restart Attempts
Torque Detection
L6-01
Selection 1
Torque Detection
L6-02
Level 1
Torque Detection Time
L6-03
1
Digital Operator
o1-03
Display Selection
Selection of Parameter
o2-19
Write during Uv
Auto-Tuning Mode
T1-01
Selection
i.8 Parameter Table
Description
0: Disabled. Drive trips on Uv1 fault
when power is lost.
1: Recover within the time set in L2-02. Uv1
is detected if power loss > L2-02.
2: Recover as long as CPU has power. Uv1
is not detected.
0: Disabled. Deceleration at the active
deceleration rate. An ov fault may occur.
1: General purpose. Deceleration is
paused when the output current exceeds
the Stall Prevention level.
4: Overexcitation Deceleration.
Decelerates while increasing motor flux.
6: Enable (Current Limit). The deceleration
rate is automatically adjusted while limiting
the regeneration current at the setting value
of the stall prevention level (L3-14).
Sets the number of times the drive may
attempt to restart after the following faults
occur: GF, LF, oC, oH1, oL1, oL3, oL4, ov,
Sto, Uv1.
0: Disabled
1: oL3 detection only active during speed
agree, operation continues after detection
2: oL3 detection always active during run,
operation continues after detection
3: oL3 detection only active during speed
agree, output shuts down on an oL3 fault
4: oL3 detection always active during run,
output shuts down on an oL3 fault
5: UL3 detection only active during speed
agree, operation continues after detection
6: UL3 detection always active during run,
operation continues after detection
7: UL3 detection only active during speed
agree, output shuts down on a UL3 fault
8: UL3 detection always active during run,
output shuts down on a UL3 fault
Sets the overtorque and undertorque
detection level.
Sets the time an overtorque or undertorque
condition must exist to trigger torque
detection 1.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of
motor poles setting in E2-04, E4-04, or
E5-04)
3: User-selected units (set by o1-10, o1-11)
Default setting is determined by parameter
A1-02, Control Method Selection.
Selects whether parameter settings can be
changed during a control circuit
undervoltage condition. To be used with 24
V Power Supply Unit Built-in model.
0: Disabled
1: Enabled
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line
Resistance
3: Rotational Auto-Tuning for V/f Control
(necessary for Energy Savings and Speed
Estimation Speed Search)
4: Stationary Auto-Tuning 2
5: Stationary Auto-Tuning 3
8: Inertia Tuning (perform Rotational Auto-
Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational
Auto-Tuning prior to ASR Gain Auto-
Tuning)
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents